Impact resistance
Boxes sit within reach of car doors, trolleys and bumpers.
Application example · Solar carport
Carport combiner boxes sit on columns within reach of cars, trolleys and passers-by. Here is how we configure a 6-string steel box that stands up to the site and is the same on every column.
The challenge
On a solar carport, the combiner boxes are mounted on the carport columns at about shoulder height, a few metres from moving cars and shoppers. The installer can’t fence them off, and the site owner expects them to look tidy for years.
A plastic box that works well on a residential roof is often the wrong choice here. The site sets four clear requirements:
Boxes sit within reach of car doors, trolleys and bumpers.
Only maintenance staff should be able to open the door.
Six parallel strings per box, each fused individually so one fault cannot feed the others.
One part number and one layout, so any technician can service any box on site.
This page shows a typical configuration and how we approach it. It does not describe a specific customer project. Final components, ratings and documents follow your approved specification.
Our solution
Steel instead of plastic. A steel enclosure resists knocks in a car park, and the safety lock keeps the door closed to anyone without a key.
A fuse on every string. Six 15A PV fuses stop a faulty string from being back-fed by the other five.
A 125A DC breaker on the output. It leaves headroom over the combined string current and gives technicians a visible point to isolate the box.
Bottom cable entry. Glands on the bottom face let cables drop straight into the cable tray running down the column, and keep rain out of the entries.
Inside the box
6 × 15A PV fuses
Protect each string individually against reverse current from the parallel strings.
125A DC breaker
Overload and short-circuit protection on the combined output, and isolation for maintenance.
500V DC SPD · 40kA max
Limits lightning-induced transients before they reach the inverter.
Steel · IP65 · safety lock
Impact-resistant, weather-sealed and tamper-proof for public sites.
6 in + 1 out + earth
Arranged on the bottom face for a straight drop into the cable tray.
Pre-wired, polarity-marked
Circuit labels and polarity markings speed up installation and inspection.
Customization
Column, wall or rail brackets sized to the posts or structure on your site.
Gland sizes and positions matched to your cable sizes and tray routing.
Inputs, outputs and fuse, breaker and SPD ratings matched to your string plan and inverter.
String labels numbered to your layout drawing, plus your logo and nameplate on the door.
How we deliver
You send the string plan, inverter details, quantity and destination, plus a photo of the mounting location if you have one.
We check fuse, breaker and SPD ratings against your module and inverter data, and propose the enclosure and cable entry layout.
You approve the drawing and component list before production. A sample or first article can be agreed at this stage.
Boxes are assembled, inspected, labelled and packed, then shipped according to the agreed delivery plan.
Soltree products
Similar project · Quotation
Send us:
Drawings by email: shawn@cnsoltree.com
See more combiner box configurationsProduct selection & quotations
Tell us your product requirements. Our team will help you find the right solution.
We use cookies to improve your experience. By continuing to visit this site you agree to our use of cookies. Privacy Policy